Wire Size Calculator

Enter the load, voltage and run length to get the minimum wire gauge by ampacity and by voltage drop; the larger of the two is the wire to buy.

Units
Circuit
V
A
ft

Panel or battery to the load, along the wire.

Conductor

NM-B conductors are 90 °C wire, but Southwire and the NEC limit the cable to the 60 °C column.

Terminal rating on the breaker and device
wires

In one conduit or cable. Over 3 derates.

Allowed voltage drop

Minimum wire size, copper

8AWG

Voltage drop decides: 12 AWG carries 16 A, but 8 AWG keeps the drop to 2.08% over 100 ft.
By ampacity
12 AWG
By voltage drop (3%)
8 AWG
Breaker for this load
20A
Voltage drop
2.5V (2.1%)
Panel120 VHotNeutral8 AWGLoad16 A100 ft one way3%5%120 V117.5 V at the loadVoltage along the run

Code check

  • 12 AWG ampacity 20 A

    Table 310.16, needs 16 A

  • 12 AWG breaker limit 20 A

    240.4(D), load needs a 20 A breaker

  • Voltage drop on 8 AWG 2.08%

    3% recommended, 210.19(A) / 215.2(A) notes

The math
  1. Ampacity needed

    16 A, noncontinuous = 16 A

  2. 12 AWG ampacity

    20 A (60 °C) × 1 ambient × 1 for 3 wires, max 20 A at 60 °C terminals = 20 A

  3. Wire for 3% drop

    2 × 12.9 × 16 A × 100 ft ÷ 3.6 V = 11,467 cmil, 8 AWG

The larger of the two sizes is the minimum. The equipment grounding wire is sized by its own table, not by this calculator.

NEC 2023 (NFPA 70): Table 310.16 ampacity, 310.15(B)(1)(1) and 310.15(C)(1) corrections, 240.4(D), K from Chapter 9 Table 8. Your state or city may adopt an older edition or add local amendments.

Match the wire to the breaker, not to the load alone: a bigger breaker later needs bigger wire. Most places require a permit and inspection for new circuits, and many only let a licensed electrician or the homeowner of a single-family house do the work. Turn the breaker off and test the wires dead before you touch them, and have a licensed electrician check anything you are unsure about.

Wire size comes from two checks, and the larger answer wins. A 16 amp load on a 120 volt circuit needs 12 AWG copper to carry the current (Table 310.16 and the 20 amp breaker it goes on), but if the load is 100 feet away, 12 AWG drops 5.27% of the voltage and you need 8 AWG to stay under the 3% the NEC recommends. Short runs are sized by ampacity; long runs by voltage drop.

How the wire size is calculated

Ampacity. Take the load in amps, multiplied by 1.25 if it runs three hours or more (a continuous load, 210.19(A)(1), as EC&M explains). Find the smallest conductor in Table 310.16 whose allowable ampacity is at least that. The column you may use is the lowest temperature rating in the circuit: the wire's insulation, and the terminals on the breaker and the device. Southwire states that NM-B cable (Romex) is limited to the 60 °C column even though its conductors are 90 °C wire.

Corrections. Above three current-carrying wires in one conduit or cable, multiply the ampacity by the Table 310.15(C)(1) factor (80% for 4 to 6 wires, 70% for 7 to 9, 50% for 10 to 20). In hot spaces, multiply by the Table 310.15(B)(1)(1) ambient factor. Derating starts from the insulation column, and the result may never exceed the terminal column.

Small conductor rule. 240.4(D) caps the breaker on small wire: 15 A on 14 AWG copper, 20 A on 12 AWG, 30 A on 10 AWG, 15 A on 12 AWG aluminum and 25 A on 10 AWG aluminum, whatever the ampacity table says.

Voltage drop. The wire must also hold the drop to 3% on a branch circuit:

CM = 2 × K × I × L ÷ (volts × 3%), with K = 12.9 for copper, 21.2 for aluminum

The first size in Chapter 9 Table 8 with at least that many circular mils passes.

Worked example: 16 A, 120 V, 100 ft

With the defaults (copper NM-B cable, 60 °C terminals, 16 A noncontinuous):

  • Ampacity: 14 AWG is 15 A at 60 °C, too small. 12 AWG is 20 A, and the 20 A breaker the load needs is allowed on 12 AWG, so 12 AWG by ampacity.
  • Voltage drop: 2 × 12.9 × 16 A × 100 ft ÷ 3.6 V = 11,467 cmil. 10 AWG has 10,380, so 8 AWG (16,510 cmil), which drops 2.50 V, 2.08%.
  • Answer: 8 AWG copper. At 50 feet, 12 AWG would pass both checks.

Tick "continuous load" and the same 16 A needs 20 A of ampacity: 12 AWG still carries it at 60 °C, with no margin.

Wire gauge and amps: Table 310.16

Allowable ampacity with up to three current-carrying conductors at 86 °F (NEC 2023 Table 310.16):

SizeCopper 60 °CCopper 75 °CCopper 90 °CAluminum 60 °CAluminum 75 °C
14 AWG15 A20 A25 Anonenone
12 AWG20 A25 A30 A15 A20 A
10 AWG30 A35 A40 A25 A30 A
8 AWG40 A50 A55 A35 A40 A
6 AWG55 A65 A75 A40 A50 A
4 AWG70 A85 A95 A55 A65 A
2 AWG95 A115 A130 A75 A90 A
1/0 AWG125 A150 A170 A100 A120 A
2/0 AWG145 A175 A195 A115 A135 A
4/0 AWG195 A230 A260 A150 A180 A

For 14 to 10 AWG the 240.4(D) breaker limits apply on top of the table. The 90 °C column is mainly for derating: six 12 AWG THHN wires in one conduit get 30 A × 80% = 24 A, still inside the 25 A limit of 75 °C terminals, and still on a 20 A breaker.

Wire size for 12 V and DC circuits

Pick the DC tab for batteries, RVs, boats, solar and low-voltage lighting. Ampacity rarely decides at 12 V; voltage drop does. A 10 A load 20 feet from a 12 V battery could run on 16 AWG by current alone (240.4(D) allows 10 A on 16 AWG), but it would lose 2.00 V, 16.7%. Holding 3% takes 8 AWG. At 24 V, 10 AWG passes. The voltage drop calculator shows every size side by side.

Copper or aluminum

Aluminum carries less current per size and has a higher K (21.2 against 12.9), so it runs one or two sizes larger. It is common and economical for feeders and service entrance cable, less so for branch circuits. The calculator starts aluminum at 12 AWG and copper at 14 AWG, the smallest sizes in the ampacity table.

What the calculator leaves to you

The equipment grounding wire has its own sizing table. Motors, air conditioners and welders have nameplate rules (minimum circuit ampacity, maximum breaker) that override the general method: use the nameplate. The inspector enforces the NEC edition your state adopted, which may be older than 2023.

Next steps

With the size known, check the breaker size for the circuit, work out the conduit fill for those wires, or turn watts into amps with the amp calculator. Planning a new service or a big addition? Start with the electrical load calculator. All tools are on the electrical calculators page.

Sizing wire for a 12V circuit in an RV, trailer or solar setup? Use this wire size calculator with 12 volts and check the run with the voltage drop calculator, because low voltage loses proportionally more over distance.