Voltage Drop Calculator

Enter the wire size, length, load and voltage to get volts dropped, percent drop, voltage at the load and the wire size that keeps it under 3%.

Units
Circuit
V
Conductor
A
ft

Distance from the panel or battery to the load, measured along the wire, not doubled.

Allowed drop

Voltage drop on 12 AWG copper

6.32V

5.27% of 120 V, so 113.68 V reaches the load.
Percent drop
5.27%
Voltage at load
113.7V
Smallest size under 3%
8 AWG
Panel120 VHotNeutral12 AWGLoad16 A100 ft one way3%5%120 V113.7 V at the loadVoltage along the run

Code check

  • Voltage drop 5.27%

    3% recommended, informational notes to 210.19(A) and 215.2(A)

  • Ampacity of 12 AWG 25 A

    Table 310.16, 75 °C, load 16 A

Go up to 8 AWG: it drops 2.50 V (2.08%) over the same run.

Every size on this run

Wire sizeDropPercentAt load
14 AWG10.04 V8.37%110.0 V
12 AWG6.32 V5.27%113.7 V
10 AWG3.98 V3.31%116.0 V
8 AWGsmallest under 3%2.50 V2.08%117.5 V
6 AWG1.57 V1.31%118.4 V
The math
  1. Voltage drop

    2 × 12.9 × 16 A × 100 ft ÷ 6,530 cmil = 6.32 V

  2. Percent

    6.32 V ÷ 120 V × 100 = 5.27%

  3. Wire for 3%

    2 × 12.9 × 16 A × 100 ft ÷ 3.6 V = 11,467 cmil, 8 AWG (16,510 cmil)

K = 12.9 for copper (ohm-cmil per foot at 75 °C, Chapter 9 Table 8). The 2 counts the wire out and back.

NEC 2023 (NFPA 70): K from Chapter 9 Table 8, ampacity from Table 310.16. Your state or city may adopt an older edition or add local amendments.

Voltage drop limits in the NEC are recommendations; the ampacity and breaker rules are not. Most places require a permit and inspection for new circuits, and many only let a licensed electrician or the homeowner of a single-family house do the work. Turn the breaker off and test the wires dead before you touch them, and have a licensed electrician check anything you are unsure about.

A 16 amp load at the end of 100 feet of 12 AWG copper on a 120 volt circuit loses 6.32 volts, a 5.27% voltage drop, so only 113.68 volts reach the load. The NEC's informational notes suggest keeping a branch circuit under 3%, which on that run takes 8 AWG copper (2.08%). Voltage drop grows with current and distance and shrinks with the wire's cross section, so a long run is the case where you size up.

How the voltage drop is calculated

The calculator uses the K method taught by electrical inspectors. K is the resistance of a copper or aluminum conductor one circular mil in area and one foot long at 75 °C: 12.9 for copper and 21.2 for aluminum, the figures IAEI Magazine derives from NEC Chapter 9 Table 8. Multiply K by the current and the one-way length, double it because current flows out on one wire and back on the other, and divide by the conductor's circular mils.

VD = 2 × K × I × L ÷ CM; three-phase: VD = 1.732 × K × I × L ÷ CM

Percent drop is VD ÷ source voltage × 100. Turn the formula around and you get the circular mils a run needs: CM = 2 × K × I × L ÷ allowed volts. The calculator does this for you and picks the first size in Table 8 that is large enough.

Worked example: 16 A over 100 ft at 120 V

Enter the defaults: single-phase, 120 V, copper, 12 AWG, 16 A, 100 ft.

  • Drop: 2 × 12.9 × 16 A × 100 ft ÷ 6,530 cmil = 6.32 V
  • Percent: 6.32 ÷ 120 × 100 = 5.27%, leaving 113.68 V at the load
  • For 3%, the run may lose 3.6 V: 2 × 12.9 × 16 × 100 ÷ 3.6 = 11,467 cmil. 10 AWG has 10,380 cmil (3.98 V, 3.31%), so the answer is 8 AWG with 16,510 cmil: 2.50 V, 2.08%

The same run at 240 V drops the same 6.32 V, but that is only 2.63%. Doubling the voltage halves the current for the same power, which is why long runs to a shop or well pump are often wired at 240 V.

Voltage drop per 100 feet, copper, 10 A

The table below is 10 amps through 100 feet one way; scale it by your amps and feet, since drop is proportional to both.

Wire sizeDrop% at 120 V% at 240 V
14 AWG6.28 V5.23%2.62%
12 AWG3.95 V3.29%1.65%
10 AWG2.49 V2.07%1.04%
8 AWG1.56 V1.30%0.65%
6 AWG0.98 V0.82%0.41%
4 AWG0.62 V0.52%0.26%

Circular mils are from NEC Chapter 9 Table 8. Aluminum drops about 64% more than copper of the same size (21.2 ÷ 12.9): 12 AWG aluminum on the worked example would lose 10.39 V, 8.66%.

3% and 5%: what the NEC says

Voltage drop appears in the NEC only as informational notes under 210.19(A) for branch circuits and 215.2(A) for feeders: about 3% on a branch circuit, and no more than 5% for feeder plus branch circuit together. IAEI points out that informational notes are not enforceable code (90.5(C)), but the installation instructions of equipment, which 110.3(B) makes you follow, often require a minimum voltage at the terminals. Pick "5%, feeder + circuit" when you are checking a subpanel feeder and the circuit beyond it as one path.

Voltage drop never replaces ampacity. A size that passes the drop check still has to carry the current under Table 310.16, which is why the result also checks the 75 °C ampacity. The wire size calculator runs both checks and gives you the larger size.

12 V and 24 V DC

Low-voltage DC is where drop bites hardest, because every volt lost is a large share of 12. The same formula applies (the 2 counts the positive and the negative wire). A 10 A load 20 feet from a 12 V battery loses:

Wire sizeDrop% at 12 V% at 24 V
16 AWG2.00 V16.67%8.33%
14 AWG1.26 V10.46%5.23%
12 AWG0.79 V6.58%3.29%
10 AWG0.50 V4.14%2.07%
8 AWG0.31 V2.60%1.30%

At 12 V you need 8 AWG to stay under 3%; at 24 V, 10 AWG does it. Use the DC tab and the 12 V or 24 V preset for RV, boat, solar and landscape lighting runs.

Three-phase circuits

For balanced three-phase loads, the multiplier is √3 (1.732) instead of 2, because the phase currents return on the other phase conductors. A 50 A motor feeder 200 feet long on 6 AWG copper at 480 V drops 8.52 V, 1.77%. Enter the line-to-line voltage (208, 240 or 480 V).

Limits of this method

K is a direct-current resistance at 75 °C. For AC conductors of 2/0 and larger, skin effect raises the resistance a little, so the true drop is somewhat higher than shown; engineers use the impedance values in Chapter 9 Table 9 for those. Conductors running cooler than 75 °C drop slightly less.

Next steps

Once the size is set, find the conduit size for those wires, check the breaker size for the load, or convert a nameplate in watts with the amp calculator. The full set of tools is on the electrical calculators page.