Amp Calculator

Pick what you know, watts, kVA, horsepower or amps, and the circuit type to get the current, the power and the breaker it needs.

Circuit
V
W

1 for heaters and lights; motors show it on the nameplate, often 0.8 to 0.9.

%

100% unless the power is a motor's output (shaft) rating.

Current

12.5A

1,500 W at 120 V single-phase.
Input power
1,500W
Apparent power
1.5kVA
Breaker, occasional use
15A
Breaker, 3 h or more
20A
The math
  1. Current

    1,500 W ÷ (120 V × 1 PF) = 12.5 A

Single-phase AC: watts = volts × amps × power factor.

NEC 2023 (NFPA 70): breaker sizes from 240.6(A), 125% for continuous loads per 210.20(A). Your state or city may adopt an older edition or add local amendments.

Motors have their own breaker and wire rules on the nameplate and in the motor article of the NEC; use them over this estimate. Most places require a permit and inspection for new circuits, and many only let a licensed electrician or the homeowner of a single-family house do the work. Turn the breaker off and test the wires dead before you touch them, and have a licensed electrician check anything you are unsure about.

To convert watts to amps, divide the watts by the volts: amps = watts ÷ volts. A 1,500 watt heater on 120 volts draws 12.5 amps; the same wattage at 240 volts draws 6.25 amps. Motors and three-phase circuits need two more numbers, the power factor and (for three-phase) √3, and the calculator handles both.

How the amp calculator works

HyperPhysics gives the base relationship: power equals voltage times current, P = V × I. In an AC circuit the average power is V × I × cos φ, where cos φ is the power factor. The U.S. Department of Energy's motor fact sheet writes three-phase power as kW = V × I × PF × √3 ÷ 1,000, with V the line-to-line voltage. Turned around for current:

Single-phase: I = W ÷ (V × PF); three-phase: I = W ÷ (1.732 × V × PF); DC: I = W ÷ V

For kVA, which already includes the power factor, the formulas drop PF: I = kVA × 1,000 ÷ V, or ÷ (1.732 × V) on three-phase.

Worked example: 1,500 W at 120 V

The defaults are a space heater, a resistive load with a power factor of 1:

  • Current: 1,500 W ÷ (120 V × 1) = 12.5 A
  • Breaker: the next standard size (240.6(A)) above 12.5 A is 15 A. If it runs for three hours or more it is a continuous load, sized at 125%: 12.5 × 1.25 = 15.6 A, so a 20 A circuit.

Watts to amps at 120 V and 240 V

WattsAmps at 120 VAmps at 240 V
500 W4.17 A2.08 A
1,000 W8.33 A4.17 A
1,500 W12.5 A6.25 A
1,800 W15 A7.5 A
2,400 W20 A10 A
3,600 W30 A15 A
4,800 W40 A20 A
7,200 W60 A30 A
10,000 W83.33 A41.67 A

These assume a power factor of 1 (heaters, water heaters, incandescent lights, toasters). For anything with a motor or an electronic power supply the current is somewhat higher than the table.

Three-phase amps

A three-phase circuit carries the power on three wires, so each carries less current. For a 10 horsepower motor with 90% efficiency and a 0.85 power factor on 480 V:

  • Output: 10 hp × 745.7 = 7,457 W. DOE converts horsepower to input kW by dividing by the efficiency: 7,457 ÷ 0.90 = 8,286 W
  • Current: 8,286 W ÷ (1.732 × 480 V × 0.85) = 11.72 A

The same motor on 208 V three-phase draws 27.1 A. Pick "Horsepower" in the power menu and set the efficiency to the nameplate figure. Motor branch circuits follow their own NEC article, so treat this as an estimate for planning, not as the size of the motor circuit.

kVA to amps

Transformers and generators are rated in kVA. A 75 kVA transformer on 208 V three-phase supplies 75,000 ÷ (1.732 × 208) = 208.2 A; at 480 V it is 90.2 A. A 25 kVA single-phase unit at 240 V gives 104.2 A. Switch to "Amps to kVA" to go the other way, for example to see what a 200 A panel at 240 V represents: 48 kVA.

Power factor and efficiency

Power factor is the share of the current that does real work. DOE describes it as the fraction of power actually delivered compared with what the same voltage and current would deliver without a phase shift, and notes it falls as a motor runs lightly loaded. Leave it at 1 for resistive loads. Efficiency matters only when the watts or horsepower you enter is a motor's shaft output: the motor draws more than it delivers.

DC amps: 12 V and 24 V

On DC there is no power factor: amps = watts ÷ volts. A 120 W inverter load on a 12 V battery draws 10 A before inverter losses; enter the inverter's efficiency to include them. Long 12 V runs lose a lot of voltage, so size the cable with the voltage drop calculator.

Next steps

Take the amps to the breaker size calculator and the wire size calculator. For a whole house, add up the loads with the electrical load calculator. If you know resistance instead of watts, use the Ohm's law calculator. All tools are on the electrical calculators page.