Breaker Size Calculator

Enter the load and whether it runs for three hours or more to get the breaker size and the smallest wire that breaker may protect.

Your load in
A

From the nameplate or the manual.

Wire
Wiring method

Use 75 °C only when the breaker, the device and the wire are all rated 75 °C. NM-B cable is limited to 60 °C.

Breaker size

30A

24 A load × 125% = 30 A; 30 A is the next standard size (240.6(A)).
Load
24A
Needed, at 125%
30A
Minimum copper wire
10 AWG
15202530354045load 24 A125%: 30 A

Swipe sideways to see the whole drawing.

Code check

  • Breaker 30 A

    at least 30 A, 125% for continuous loads (210.20(A))

  • 10 AWG copper 30 A

    Table 310.16, 60 °C column, at least 30 A

  • 10 AWG breaker limit 30 A

    240.4(D) small conductor rule

Common circuits, copper

BreakerNM-B, 60 °C75 °CTypical use
15 A14 AWG14 AWGLights, bedroom and living room outlets
20 A12 AWG12 AWGKitchen countertop, bathroom, laundry and garage outlets
30 A10 AWG10 AWGElectric dryer, water heater, small EV charger
40 A8 AWG8 AWGCooktop, larger EV charger
50 A6 AWG8 AWGElectric range, EV charger, hot tub
60 A4 AWG6 AWGSubpanel, large EV charger, tankless water heater
The math
  1. Continuous load

    24 A × 1.25 = 30 A

  2. Breaker

    next standard size at or above 30 A = 30 A

  3. Wire

    smallest copper with at least 30 A at 60 °C = 10 AWG (30 A)

The breaker protects the wire, so the wire must be rated for the breaker, not just for the load.

NEC 2023 (NFPA 70): 240.6(A) standard sizes, 125% rule in 210.19(A)(1) and 210.20(A), Table 310.16, 240.4(D). Your state or city may adopt an older edition or add local amendments.

Never put a bigger breaker on existing wire to stop it tripping: the wire is the part that overheats. Most places require a permit and inspection for new circuits, and many only let a licensed electrician or the homeowner of a single-family house do the work. Turn the breaker off and test the wires dead before you touch them, and have a licensed electrician check anything you are unsure about.

A breaker must be at least as large as the load, and 125% of the load if it runs three hours or more. Then round up to the next standard size. A 24 amp EV charger runs for hours, so it needs 24 × 1.25 = 30 amps: a 30 amp breaker on 10 AWG copper. A 12.5 amp heater used now and then fits a 15 amp breaker; left on all evening it needs 15.6 amps, so a 20 amp circuit.

How the breaker size is calculated

Continuous or not. The NEC calls a load continuous when its maximum current is expected to last three hours or more: EV chargers, water heaters, space heaters, pool pumps, lighting in a shop that runs all day. EC&M sums up the rule in 210.19(A)(1), 210.20(A) and 215.3: branch-circuit conductors and overcurrent protection are sized at 125% for continuous loads. The rest of the load counts at 100%.

Breaker ≥ noncontinuous amps + 1.25 × continuous amps, rounded up to a 240.6(A) size

Standard sizes. Table 240.6(A) lists the standard ratings: 10, 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200 amps and up. The calculator picks the first one at or above the amps needed.

Wire for the breaker. The breaker protects the wire, so the wire's ampacity in Table 310.16 must be at least the breaker rating, in the temperature column the wiring allows. Southwire's data for Romex NM-B limits it to the 60 °C column. On top of that, 240.4(D) caps 14 AWG copper at 15 A, 12 AWG at 20 A and 10 AWG at 30 A.

Worked example: a 24 A EV charger

The calculator opens on it: 24 A, continuous, copper, NM-B.

  • 24 A × 1.25 = 30 A needed
  • 30 A is a standard size, so a 30 A breaker
  • Copper at 60 °C: 12 AWG carries 20 A, 10 AWG carries 30 A, and 240.4(D) allows 30 A on 10 AWG: 10 AWG

Enter it as watts instead and you get the same: 5,760 W ÷ 240 V = 24 A. A 32 A charger needs 40 A and 8 AWG; a 40 A charger needs a 50 A breaker.

Breaker and wire size chart

The smallest copper wire each breaker may protect, from Table 310.16 and 240.4(D):

BreakerCopper, NM-B (60 °C)Copper, 75 °CAluminum, 75 °C
15 A14 AWG14 AWG12 AWG
20 A12 AWG12 AWG10 AWG
30 A10 AWG10 AWG8 AWG
40 A8 AWG8 AWG8 AWG
50 A6 AWG8 AWG6 AWG
60 A4 AWG6 AWG4 AWG

The 75 °C column applies only when the wire, the breaker and the equipment terminals are all rated 75 °C, typically individual THHN wires in conduit. A 50 A circuit in NM-B cable needs 6 AWG because 8 AWG is only 40 A at 60 °C.

What changes the answer

  • Long runs. Voltage drop can call for a bigger wire than the breaker does, never a smaller one. Check with the voltage drop calculator.
  • Several wires together. More than three current-carrying wires in a conduit lose ampacity (Table 310.15(C)(1)); the wire size calculator applies it.
  • Motors and air conditioners. Their nameplates list a minimum circuit ampacity and a maximum breaker, which take precedence over this general method.
  • A breaker that trips. A breaker tripping on a circuit whose wire matches it is doing its job. Moving the load to its own circuit is the fix; a larger breaker on the same wire is a fire risk and a code violation.

From watts to breaker

If the nameplate gives watts, divide by the voltage: a 4,500 W water heater at 240 V draws 18.75 A. Counted as a continuous load, 18.75 × 1.25 = 23.4 A, which rounds up to a 25 A breaker, and 10 AWG copper because 12 AWG is capped at 20 A. The amp calculator converts watts, kVA and horsepower, including three-phase.

Next steps

Planning a panel upgrade or a new service? Add up every circuit with the electrical load calculator. All electrical tools are on the electrical calculators page.