Baseboard Heater Calculator

Enter the room size and ceiling height to get the watts of baseboard heat, the heater lengths to buy and the current they draw.

Units
Room length
ft
in
Room width
ft
in
ft

10 W per sq ft assumes 8 ft; above that the rule becomes 1.25 W per cubic foot.

W

W per sq ft. 10 is the rule for an insulated room with 8 ft ceilings (Stelpro).

%

Stelpro suggests adding a few percent for weak insulation or oversized windows.

Circuit voltage

One under each window heats most evenly. More are added if one heater can't give enough.

Baseboard heat for 144 sq ft

1,440watts

Buy one 6 ft 1,500 W heater: 1,500 W and 6.3 A at 240 V.
1,500 W72 in12 ft

Swipe sideways to see the whole drawing.

Heater length
6ft
Current
6.25A
Heat output
5,118BTU/h
The math
  1. Floor area

    12 ft × 12 ft = 144 sq ft

  2. Watts needed

    144 sq ft × 10 W = 1,440 W

  3. Per heater

    1,440 W ÷ 1 = 1,440 W, so the 6F1500 (72 in)

  4. Current

    1,500 W ÷ 240 V = 6.25 A

Material list

144 sq ft room, 1,440 W at 240 V

QuantityItem
1heater

Baseboard heater, 72 in, 1,500 W 240/208 V

Sized like the Cadet 6F1500

1thermostat

Line-voltage thermostat, double pole

Built-in kit or wall thermostat rated for the total current

6.3 A of electric heat needs its own circuit sized for it. Work out the breaker in the breaker size calculator and the wire in the wire size calculator, and have a permit and inspection where your building department requires one. Keep 12 in clear of furniture and drapes and do not mount below outlets.

A 12 × 12 ft room (144 sq ft) with an 8 ft ceiling needs about 1,440 watts of electric baseboard heat at the usual 10 watts per square foot. That is one 6 ft, 1,500 W heater, which draws 6.25 amps on a 240 V circuit. Taller ceilings, weak insulation and big windows push the number up.

How baseboard heater wattage is calculated

Stelpro, a heater maker, gives the rule: "Multiply the area in feet by 10" for rooms with 8 ft ceilings. Above 8 ft it switches to volume, 1.25 W per cubic foot, which is the same as scaling 10 W per sq ft by height ÷ 8. The calculator does exactly that and then adds your allowance for poor insulation or large windows.

Watts = floor area (sq ft) × 10 W × (ceiling ÷ 8 ft) × (1 + extra %)

Amps = heater watts ÷ volts

Stelpro's own example: a 400 sq ft room with 9 ft ceilings needs 400 × 9 × 1.25 = 4,500 W. Enter 20 × 20 ft and 9 ft and the calculator shows the same 4,500 W.

How many feet of baseboard heater?

Heaters are sold by length and wattage. The Cadet F series product sheet lists these 240 V models (208 V output in brackets):

LengthModelWatts at 240 V (208 V)Amps at 240 V
24 in2F350350 (262)1.5
30 in2F500500 (375)2.1
36 in3F750750 (563)3.1
48 in4F10001,000 (750)4.2
60 in5F12501,250 (937)5.2
72 in6F15001,500 (1,125)6.3
96 in8F20002,000 (1,500)8.3
96 in8F25002,500 (1,875)10.4

From 36 in up that is 250 W per foot, the figure most people quote, but the 30 in 500 W model shows it is not a law: pick from the table, not by dividing. The 120 V versions stop at 6 ft and 1,500 W (12.5 A).

The calculator splits the watts over the number of heaters you ask for and picks the shortest model that covers each share. For the 144 sq ft room, one heater means the 72 in 1,500 W model; two heaters (one under each of two windows) means two 36 in 750 W models, 1,500 W in total.

Worked example: 20 × 20 ft room, 9 ft ceiling

  • Watts: 400 sq ft × 10 × 9 ÷ 8 = 4,500 W.
  • One heater cannot do it (the biggest is 2,500 W), so the calculator uses at least two: 2,250 W each, two 96 in 2,500 W heaters, 5,000 W and 20.8 A at 240 V.
  • Set three heaters instead and each share is 1,500 W: three 72 in 1,500 W heaters, 4,500 W and 18.75 A, spread along three walls.

240 V, 208 V or 120 V

Most baseboard heat runs on 240 V. In apartments and commercial buildings the supply is often 208 V, and Cadet notes that 240 V models "can be used at 208 volts. Wattage equals 75% of 240v rated wattage." The 144 sq ft room at 208 V therefore needs the 96 in 2,000 W model to reach 1,500 W, drawing 7.2 A. At 120 V the same room takes the 1,500 W 120 V model at 12.5 A, twice the current of the 240 V version, which is why larger rooms are almost always wired at 240 V.

Circuits and breakers

Heater current decides the circuit. Add every heater on the circuit, then size the breaker and wire for that total in the breaker size calculator and the wire size calculator. If you are adding heat to an existing panel, check the spare capacity first with the electrical load calculator. All Cadet baseboards need a thermostat, built in or on the wall, rated for the current it switches.

Where to put the heaters

Cadet's installation notes: under a window works best, keep at least 12 in from furniture and from drapes hanging above, and never mount a heater below an electrical outlet. The drawing under the result places each heater under its own window on your longest wall, to scale.

Watts to BTU

One watt is 3.412 BTU/h (EIA), so 1,500 W of baseboard heat is 5,118 BTU/h. To compare electric heat with a gas heater or a heat pump for the same room, use the heat tab of the BTU calculator, which sizes rooms by climate zone instead of a flat 10 W per sq ft.