Soffit Calculator

Soffit area = eave length x depth; 80 ft of eave 12 in deep is 80 sq ft, or 8 vinyl panels of 12 in x 12 ft with 10% waste.

Units
Eave length with soffit
ft
in

Add up every run along the house where there is an overhang. Both long sides of a 40 ft house is 80 ft.

Gable end (rake) soffit
ft
in

Only if the gable ends have a boxed overhang. Leave at 0 for open rakes.

in

Level, from the wall to the back of the fascia. Nailing strips are needed past 16 in (Polymeric Exteriors Council).

Net free area per sq ft is a typical value from Air Vent: check the box of the product you buy.

%

Percent of the soffit area you make vented panels. The rest stays solid.

sq ft

Half of the 1/150 attic vent area has to come in at the soffit. Enter it to check.

in

12 in is common.

ft

12 ft is common.

%

Cuts at corners and ends.

ft

Check your supplier's length.

ft

Board or coil length.

Soffit panels

8panels

80 sq ft of soffit (0.8 squares), 80 ft of eave at 12 in deep, with 10% waste. Each panel is cut into 12 pieces of 11 ½ in.
Soffit area
80sq ft
J and F-channel pieces
13pieces
Fascia pieces
7pieces
Soffit net free area
1,120sq in
J-channelF-channelfascia100% vented12 in

Soffit vent check

Half the 1/150 attic vent area is 720 sq in of net free intake. This soffit gives 1,120 sq in. That covers the intake. You need about 64% of this soffit vented.

The math
  1. Soffit area

    80 ft of eave × 12 in deep = 80 sq ft

  2. Pieces

    80 ft ÷ 12 in panel width = 80 pieces, × 1.1 waste = 88 pieces

  3. Panels

    88 pieces ÷ 12 per 12 ft panel (cut 11 ½ in, ½ in short for expansion), rounded up = 8 panels

  4. Channel

    80 ft at the wall + 80 ft at the fascia = 160 ft ÷ 12 ft 6 in = 13 pieces

  5. Fascia

    80 ft ÷ 12 ft = 7 pieces

  6. Intake needed

    1,500 sq ft ÷ 150 ÷ 2 × 144 in² per ft² = 720 sq in

Nail the receiving channels every 8 to 12 in, centered in the slots.

Material list

80 ft of eave, 12 in deep, 10% waste.

QuantityItem
8panels

Soffit panels 12 in × 12 ft

Perforated, 14 sq in per sq ft

13pieces

J-channel or F-channel, 12 ft 6 in

wall side and fascia side

7pieces

Fascia, 12 ft

Boxed eaves hide the ventilation path. Keep at least 1 in of clear air space between the insulation and the roof sheathing at every soffit vent (IRC R806.3), and use baffles where the insulation is blown in.

Soffit area = eave length × soffit depth. Eaves of 80 ft in total and 12 in deep make 80 sq ft of soffit, which takes 8 vinyl panels of 12 in × 12 ft with 10% waste, plus 13 pieces of J or F-channel and 7 pieces of fascia. If the soffit carries the attic's intake vents, a perforated panel gives 14 sq in of vent area per sq ft.

How the soffit is calculated

The soffit is the underside of the eave, from the house wall out to the fascia. Its area is the length of eave times its depth, measured level. Each piece of vinyl or aluminum soffit runs from the wall to the fascia, so pieces stand side by side along the eave, one panel width each.

Area = eave length × depth  ·  Pieces = eave length ÷ panel width × (1 + waste)  ·  Panels = pieces ÷ (panel length ÷ cut length)

Worked example: 80 ft of eave at 12 in deep is 80 sq ft, 0.8 square. With 12 in wide panels that is 80 pieces, and 88 with 10% waste. Installers cut each piece ½ in short of the wall-to-fascia distance for expansion (Polymeric Exteriors Council), so a 12 ft panel gives 12 pieces of 11½ in. 88 ÷ 12 = 7.33, so you buy 8 panels. Channel runs along both the wall and the fascia: 2 × 80 = 160 ft, and at 12½ ft per piece that is 12.8, or 13 pieces. Fascia is 80 ft ÷ 12 ft, or 7 pieces. Check the lengths your supplier sells: the piece lengths are inputs.

Soffit, fascia and J-channel

The receiving channel holds the soffit at each end. J-channel or F-channel goes on the wall and on the fascia. Nail channels every 8 to 12 in, with the nail centered in the slot. If the eave is deeper than 16 in, the panels need a nailing strip, at least 4 in wide, across the middle. Adding rake soffit at the gable ends adds to the run and, if you turn on the fascia toggle, to the fascia length too. Soffit usually rides along with the siding order: work that out in the vinyl siding calculator.

Soffit vent calculator: how much of the soffit should be vented

Attic intake comes through the soffit. The IRC sets the total vent area at 1/150 of the attic floor area (R806.2), and a balanced system puts half of it low at the eaves. For a 1,500 sq ft attic that is 1,500 ÷ 150 = 10 sq ft, or 1,440 sq in, of which 720 sq in is intake. Air Vent lists perforated aluminum soffit at 14 sq in per sq ft, so the 80 sq ft in this example gives 1,120 sq in if every panel is perforated. You need 720 ÷ (80 × 14) = 64% of the soffit vented, and the calculator says so when you enter the attic floor area. Lanced soffit is much lower, quoted at 4 to 7 sq in per sq ft, and a continuous strip vent gives 9 sq in per ft. Product numbers vary: read the box of the vent you buy.

Intake typeNet free area (Air Vent table)
Perforated aluminum soffit14 sq in per sq ft
Continuous soffit vent strip9 sq in per ft
Undereave vent 16 × 8 in56 sq in each
Undereave vent 16 × 4 in28 sq in each

Keep the air path open

A vented soffit only works if air can get past the insulation. Leave a gap between the insulation and the roof sheathing at each vent (the IRC's R806.3 asks for 1 in, as quoted in the Air Vent guide) and fit baffles if you blow in insulation.

What to work out next

Now size the ridge or box vents that pair with these soffits in the attic ventilation calculator. The gutters hang on the same fascia: pick a size with the gutter size calculator and set the fall with the gutter slope calculator. If the attic gets new insulation, the blown-in insulation calculator counts the bags. See all roofing tools in the roofing and siding calculators.