Tankless Water Heater Size Calculator

Tankless Btu/h = GPM × temperature rise × 500 ÷ efficiency; two showers and a kitchen sink at a 65 °F rise need 6.5 GPM and about 222,000 Btu/h.

Units
Hot water running at the same time

2.5 gpm each

4 gpm each

1 gpm each

1.5 gpm each

1.5 gpm each

2 gpm each

gpm

Add a hot tub fill, a utility sink or a second bathroom here.

Mid-Atlantic: winter groundwater about 55 °F. Change the number below if you know yours.

°F

13 °C. Size for winter: the water is coldest when you use the most.

°F

120 °F is the recommended safe setting.

Heater type

Flow you need at a 65 °F rise

6.5gpm

Look for a gas heater of at least 223,000 Btu/h input that delivers 6.5 gpm at a 65 °F rise.
Temperature rise
65°F
Heat into the water
211,166Btu/h
Gas input needed
222,279Btu/h
Efficiency used
95%
Fixtures on
3
55 °F in120 °F outrise 65 °F at 6.5 gpm

GPM by temperature rise for a 223,000 Btu/h input

Temperature rise (°F)4050607080
Flow (gpm)10.68.57.16.15.3
The math
  1. Flow

    2 × 2.5 gpm + 1 × 1.5 gpm = 6.5 gpm

  2. Temperature rise

    120 °F set − 55 °F incoming = 65 °F

  3. Heat into the water

    6.5 gpm × 65 °F × 8.33 lb/gal × 60 min/h = 211,166 Btu/h

  4. Gas input

    211,166 Btu/h ÷ 0.95 efficiency = 222,279 Btu/h

Efficiencies (0.95 condensing, 0.82 standard gas, 0.98 electric) sit inside the ranges tankless makers publish. Check the rated flow at your rise on the spec sheet.

Tankless water heater Btu/h = GPM × temperature rise × 500 ÷ efficiency. Two showers and a kitchen sink running at once (6.5 GPM) with 55 °F incoming water need a 65 °F rise, which is 211,166 Btu/h into the water and about 222,000 Btu/h of gas input at 0.95 efficiency, or 63 kW of electric power.

How tankless water heater sizing works

A tankless heater has no storage, so its size is the flow it can heat, not gallons. Two numbers set it: how many gallons per minute (GPM) you run at once, and the temperature rise, the gap between the cold water entering and the hot water you want.

temperature rise = set temperature − incoming water temperature

Btu/h into the water = GPM × rise × 8.33 lb per gal × 60 min per h (about 500 × GPM × rise)

gas input = Btu/h into the water ÷ efficiency; electric kW = Btu/h ÷ 3,412 ÷ efficiency

The set temperature defaults to 120 °F, the safe setting the Consumer Product Safety Commission recommends. Size for winter, when the groundwater is coldest and you use the most hot water.

Worked example: two showers and a kitchen sink

StepCalculationResult
Flow2 showers × 2.5 GPM + 1 kitchen sink × 1.5 GPM6.5 GPM
Rise120 °F − 55 °F (Mid-Atlantic winter)65 °F
Heat into the water6.5 × 65 × 499.8211,166 Btu/h
Gas, condensing (0.95)211,166 ÷ 0.95222,279 Btu/h
Gas, standard (0.82)211,166 ÷ 0.82257,519 Btu/h
Electric (0.98)211,166 ÷ 3,412 ÷ 0.9863.2 kW

That electric figure is 263 A at 240 V, more than the 200 A service many homes have, so a whole-house electric unit only suits small loads or warm-water climates. Check the wire size and panel before you choose one.

Tankless water heater GPM by fixture

The calculator counts each fixture at the top of its range so the unit is not undersized:

FixtureGPM usedTypical range
Shower2.5 (2.0 with low-flow heads)2.0 to 2.5
Bathtub fill4.04.0 to 6.0
Bathroom sink1.00.5 to 1.0
Kitchen sink1.51.5 to 2.0
Dishwasher1.51.0 to 1.5
Clothes washer2.01.5 to 2.0

Count only what really runs together. Two showers and a dishwasher at once is 6.5 GPM; a tub fill plus a shower is 6.5 GPM too. Use the "anything else" field for a hot tub fill or a utility sink.

Incoming water temperature by state

Pick your state and the calculator fills the winter groundwater temperature from this regional table (Tankless Geek):

RegionWinter waterStates in this calculator
Far north40 °FAK
Northern states45 °FME, NH, VT, MA, CT, RI, NY, MI, WI, MN, ND, MT
Pacific Northwest52 °FWA, OR
Midwest and Great Plains50 °FSD, NE, IA, IL, IN, OH, KS, MO, WY, CO, ID, UT
Mid-Atlantic55 °FPA, NJ, DE, MD, DC, VA, WV
Southern states58 °FKY, TN, NC, SC, OK, AR, TX
California58 °FCA
Southwest desert60 °FAZ, NV, NM
Deep South62 °FGA, AL, MS, LA
Florida and Gulf Coast68 °FFL, HI

States the source table does not name are placed in the nearest climate group. Water temperature varies inside a state and with the season, so overwrite the number if you know yours. Minnesota at 45 °F is a 75 °F rise: two showers (5 GPM) need 187,425 Btu/h into the water, about 197,000 Btu/h of gas input. Florida at 68 °F is a 52 °F rise: the 6.5 GPM example needs 168,932 Btu/h, about 178,000 Btu/h of input.

GPM at each temperature rise

A heater's rating is a fixed heat output, so the flow it delivers falls as the rise grows. At 0.95 efficiency:

Temperature rise (°F)4050607080
150,000 Btu/h unit (GPM)7.15.74.84.13.6
200,000 Btu/h unit (GPM)9.57.66.35.44.8

If your GPM at your rise is more than one unit delivers, either drop a fixture from the "at once" list or plan two units.